The Quinta Ace 160 is one of the most advanced wall-hung boilers on the market. It can work as an extension of the Quinta Pro range giving you the ability to mix and match cascades. This enables you to achieve the closest possible match to your required load. With plant room space at a premium, the ability to move large outputs away from the floor and onto the wall makes the overall design process easier.

  • Built on the Quinta platform - tried and tested technology  
  • Class-leading power output to physical size ratio - plant room space reduction and access through doors and lifts easier
  • Next generation human machine interface gives the customer great flexibility in terms of external management
  • Suitable for use on sealed systems and open-vented installations
  • Perfect for use in both new and retrofit installations
  • Cascade up to eight boilers in-line or back-to-back - time saving installation with on-site assembly
  • Mixed cascade (with Quinta Pro) available - exact matching of heat output requirements
  • Time-saving installation with on-site assembly
  • Control supplied as standard with all functions as the Quinta Pro - time and temperatures can be set and controlled by the end user
  • In-built 0-10V and free volt contacts - can connect to any BMS without additional parts needed
  • Multiple flueing capabilities - flexible installation in new and exiting buildings
  • Cleanable heat exchanger, as with all Quinta models - dry side can be examined and descaled. Cleaning tool and gaskets available
  • 'Click and Go' condensate drain underneath (not inside) - ease of installation
  • Low NOx ErP Ecodesign 2018 EN15502 Pt1 2015 Class VI - future-proof for emissions regulation
  • Internal lighting - aids servicing in plant rooms
  • Digital diagnostic display and remote signalling options - easy operation and maintenance

LITERATURE FOR QUINTA ACE

Download all literature and product documents for the Quinta Ace by clicking the links below.

TECHNICAL INFORMATION

Click to download the technical specification for the Quinta Ace 160 in PDF format

 

QUINTA ACE 160

PERFORMANCE

Nominal heat output central heating operation @ 80/60°C kW (min-max)*

31.5-152.9

Nominal heat output central heating operation @ 50/30°C kW (min-max)*

34.6-161.5

Nominal input (Hi) (min-max)

32-156

EFFICIENCY

SBEM seasonal efficiency GCV

95.5%

Efficiency – full load 100% NCV

98.0%

Efficiency – part load 30% NCV

107.9%

Eco design useful efficiency @ 80/60°C (100% full load) GCV

88.3%

Eco design useful efficiency @ 50/30°C (30% part load) GCV

97.2%

Energy labelling seasonal space efficiency GCV

n/a

ErPD efficiency rating

n/a

Annual energy consumption kWh

n/a

Gas connection size BSP inches

1” male thread

GAS

Standard fuel

Natural gas

Optional fuel adjustment – see installation & service manual

n/a

Gas consumption NG m3/h

3.4-16.5

Max gas consumption LPG m3/h

n/a

Min/max gas inlet pressure NG mbar

17-25

Min/max gas pressure LPG mbar

n/a

Gas connection size BSP inches

1” male thread

FLUE (CONCENTRIC CONNECTION SUPPLIED AS STANDARD)

Flue diameter mm I/D

100

Air inlet diameter mm I/D

150

Min/max flue gas flow rate kg/h

277 max

Min/max flue gas flow rate g/s

76.9 max

Min/max flue gas temperature °C

30-62.3

Max counter pressure Pa

200

HYDRAULICS

Water content litres

17.0

Resistance @ 11°C ΔT mbar

510

Hydraulic resistance @ 20°C ΔT mbar

170

Nominal flow rate @11°C ΔT l/s

3.31

Nominal flow rate @ 20°C ΔT l/s

1.82

Minimum flow rate m3/hr

0.4

Condensate connection

Φ32mm

Connection size BSP

1¼” male thread

Standard operating temperature °C **

20-90

Max operating temperature °C

90

Max water temperature °C

110

Max water operating pressure bar

4

Min water operating pressure bar

0.8

Min operating pressure bar

0.5 o/v

GENERAL

Dry weight kg

147

Min mounting weight without front panel

123

Dimension (WxHxD)

600x1045x602

NOx (Dry, 0% 02) Mg/kWh

35

Noise levels dB(A) at 1 metre

55

Eco design sound power levels LWA indoors dB

63

Standby heat Loss

0.191

ELECTRICAL

Nominal power supply

230v x 1Ph x 50hz

Start current amps

2.2

Power consumption W

47-275

Modulating input V dc

0-10

Fuse rating amps

6.3

Controls voltage

24 (max 4va)

Electrical protection index VAC

X1B

*Gas consumption based on lower heating value under standard heating conditions: T=288.15K, p=1013.25mbar. Gag 30.33, G25 29.25, G31 88.00 MJ/m3

**Open vented option maximum operating temperature 75°C

  • St Davids Cathedral

    Cathedral selects Quinta Ace 160 as most suitable boiler for refurbishment.

    Remeha boilers were selected due to the brand’s reputation for high quality and high performance.

You may be interested in...

ENGINEERING EFFICIENCY SINCE 1935