The Gas 120 Ace provides maximum energy efficiency and the Remeha weather compensator options ensure the boiler closely matches the system demand. Conventional and room-sealed flue system capability enables the boiler to be sited almost anywhere within a building.
Download all literature and product documents for the Gas 120 Ace by clicking the links below.
Click here for literature on controls.
Click to download the technical specification for the Gas 110 in PDF format
GAS 120 Ace 65 |
GAS 120 Ace 90 |
GAS 120 Ace 115 |
|
---|---|---|---|
PERFORMANCE |
|||
Nominal heat output central heating operation @ 80/60°C kW (min-max)* |
12.0-61.5 61.5 |
14.1-84.2 84.2 |
118.9-103.9 103.9 |
Nominal heat output central heating operation @ 50/30°C kW (min-max)* |
13.5-65.0 65.0 |
15.8-89.5 89.5 |
21.2-109.7 109.7 |
Nominal input (Hi) (min-max) |
12.2-62.0 62.0 |
14.6-86.0 86.0 |
19.6-107.0 107.0 |
EFFICIENCY |
|||
SBEM seasonal efficiency GCV |
97.6 |
95.7 |
95.4 |
Efficiency – full load 100% NCV |
99.2 |
97.9 |
97.1 |
Efficiency – part load 30% NCV |
110.4 |
108.1 |
108 |
Useful efficiency @ 80/60°C (100% full load) GCV |
89.4 |
88.2 |
87.5 |
Useful efficiency @ 50/30°C (30% part load) GCV |
99.5 |
97.4 |
97.3 |
Seasonal space efficiency GCV |
94 |
N/A |
N/A |
ErPD efficiency rating |
A |
N/A |
N/A |
GAS |
|||
Standard fuel |
Natural gas |
Natural gas |
Natural gas |
Optional fuel adjustment – see installation & service manual |
LPG |
LPG |
LPG |
Max gas consumption NG m3/h |
6.6 |
9.1 |
11.7 |
Max gas consumption LPG kg/h |
2.5 |
1.5 |
2.0 |
Min/max gas inlet pressure NG mbar |
17 - 25 |
17 - 25 |
17 - 25 |
Min/max gas pressure LPG mbar |
37 - 50 |
37 - 50 |
37 - 50 |
Gas connection size BSP inches |
3/4" |
3/4" |
3/4" |
FLUE (CONCENTRIC CONNECTION SUPPLIED AS STANDARD) |
|||
Flue diameter mm I/D |
100 |
100 |
100 |
Air inlet diameter mm I/D |
150 |
150 |
150 |
Min/max flue gas flow rate kg/h |
21 - 104 |
28 - 138 |
36 - 178 |
Average flue gas temperature (75/60°C) |
30 - 120 |
30 - 120 |
30 - 120 |
Maximum counter pressure PA |
100 |
160 |
220 |
HYDRAULICS |
|||
Water content litres |
7.1 |
10.1 |
10.1 |
Hydraulic resistance @ 20°C ΔT mbar |
130 |
140 |
250 |
Resistance @ 11°C ΔT mbar |
430 |
463 |
826 |
Nominal flow rate @ 20°C ΔT l/s |
0.74 |
1.01 |
1.24 |
Nominal flow rate @11°C ΔT l/s |
1.34 |
1.83 |
2.26 |
Minimum flow rate I/hr |
290 |
340 |
455 |
Condensate connection |
25mm OD |
25mm OD |
25mm OD |
Connection size BSP |
1 1/4" (M) |
1 1/4" (M) |
1 1/4" (M) |
Standard operating temperature °C |
20 - 90 |
20 - 90 |
20 - 90 |
Max operating temperature °C |
90 |
90 |
90 |
Max water operating pressure bar |
4 |
4 |
4 |
Min water operating pressure bar |
0.8 |
0.8 |
0.8 |
Min water operating pressure bar open vented* (0V) |
0.3 |
0.3 |
0.5 |
GENERAL |
|||
Dry weight kg |
98 |
109 |
109 |
Dimension (WxHxD) (Includes flow/return and gas pipework) |
600x1360x605 |
600x1582x605 |
600x1582x605 |
NOx (Dry, 0% 0) Mg/kWh EN483/15420 |
29 |
41 |
41 |
Noise levels dB(A) at 1 metre |
40 |
45 |
45 |
Eco Design Sound Power Levels LWA indoors dB |
55 |
61 |
60 |
Standby heat Loss kWh/24hr |
0.114 |
0.119 | 0.119 |
ELECTRICAL |
|||
Nominal power supply |
230v - 1ph |
230v - 1ph |
230v - 1ph |
Power consumption-Full Load W |
25 - 92 |
24 - 124 |
34.3 - 180 |
Modulating input V dc |
0-10 |
0-10 |
0-10 |
Fuse rating amps |
6.3 |
6.3 | 6.3 |
Controls voltage |
24 (4va) |
24 (4va) |
24 (4va) |
Insulation class IP |
IPX1B |
IPX1B |
IPX1B |
*Open vented option maximum operating temperature 75°C |
ENGINEERING EFFICIENCY SINCE 1935