A compact, lightweight structure makes the Gas 210 Ace floor standing boiler quick and easy to install. It has the capacity to be installed back-to-back, which provides added flexibility in space-saving design. The optional secondary return feature makes this boiler particularly suitable with heating technologies that use low-grade heat, such as heat pumps or underfloor circuits.

Features and Benefits

High-efficiency

High-efficiency floor standing boiler up to 95.8% GCV Seasonal Efficiency – reliable, high-performance operation

Compact size

Extremely compact dimensions and ability to be installed back-to-back – space-saving solution, ideally suited for modular configurations

Environmentally friendly

Low Class 6 NOx emission levels from 33mg/kWh (0% O2 dry) – low pollutant emissions meeting all environmental legislation

Energy efficient

Options for direct weather compensation – close matching of heat demand at all times for maximum energy efficiency

Maximum efficiencies

Optional secondary return feature – maximum efficiencies with low-grade heat technologies

Easy operation

Digital diagnostic display and remote signalling options – easy operation and maintenance

Flexible

For single use, cascade or in conjunction with condensing boilers

Quiet operation

Low noise starting from 48dBA max at 1m for a quiet operation
Show More
Show Less

Technical Specification

Model

80

120

160

200

3 sections 4 sections 5 sections 6 sections
Performance
Nominal heat output central heating operation @ 80/60°C kW (min-max)18-8722-12029-16639-200
Nominal heat output central heating operation @ 50/30°C kW (min-max)20-9324-12933-17944-217
Nominal input (Hi) (min-max)19-8923-12331-17041-205
Efficiency
SBEM seasonal efficiency GCV95.8%95.66%95.5%95.74%
Efficiency – full load 100% NCV97.4%97.5%97.5%97.6%
Efficiency – part load 30% NCV108.6%108.1%108.3%108.4%
Eco design useful efficiency @ 80/60°C (100% full load) GCV87.7%87.8%87.8%87.8%
Eco design useful efficiency @ 50/30°C (30% part load) GCV97.7%97.5%97.3%97.6%
Gas
Standard fuelNatural gasNatural gasNatural gasNatural gas
Optional fuel adjustment – see installation & service manualLPG (propane)LPG (propane)LPG (propane)LPG (propane)
Max gas consumption NG m3/h9.4131821.7
Max gas consumption LPG m3/h3.64.878.4
Min/max gas inlet pressure NG mbar17-2517-2517-2517-25
Min/max gas pressure LPG mbar37-5037-5037-5037-50
Gas connection size BSP inches1¼” male thread1¼” male thread1¼” male thread1½” male thread
Flame protectionIonisationIonisationIonisationIonisation
IgnitionElectronicElectronicElectronicElectronic
Flue (concentric connection supplied as standard)
Flue diameter mm I/D150150150150
Air inlet diameter mm I/D150150150150
Mass flue gas flow rate kg/h27-15037-19739-28765-345
Max counter pressure PA130130130130
Hydraulics
Water content litres12162024
Hydraulic resistance @ 11°C ΔT mbar549449566599
Hydraulic resistance @ 20°C ΔT mbar165135170180
Nominal flow rate @11°C ΔT l/s1.892.613.614.33
Nominal flow rate @ 20°C ΔT l/s1.041.431.982.38
Minimum flow rate I/hr1120148621422585
Condensate connection32mm OD32mm OD32mm OD32mm OD
Connection size BSP1¼” male thread1¼” male thread1¼” male thread1½” male thread*
Standard operating temperature °C20-9020-9020-9020-90
Max operating temperature °C90909090
Max water temperature °C110110110110
Max water operating pressure bar6666
Min water operating pressure bar0.80.80.80.8
General
Dry weight kg115135165188
Dimension (WxHxD)1190 x 1368 x 4501190 x 1368 x 4501190 x 1368 x 4501190 x 1368 x 450
NOx (Dry, 0% 02) Mg/kWh56494452
Noise levels dB(A) at 1 metre Less than 59 Less than 59 Less than 59 Less than 59
Eco design sound power levels LWA indoors dB67676767
Standby heat Loss0.210.210.210.21
Electrical
Nominal power supply230v x 1Ph x 50hz230v x 1Ph x 50hz230v x 1Ph x 50hz230v x 1Ph x 50hz
Start current amps26-10328-16749-19648-306
Modulating input V dc0-100-100-100-10
Fuse rating amps6.36.36.36.3
Controls voltage24 (max 4va)24 (max 4va)24 (max 4va)24 (max 4va)
Insulation class IPIPX1**IPX1**IPX1**IPX1**

*with supplied 1¼” > 1½" reducer bushings
**IP20 when appliance is fitted with a B23 conventional flue