Remeha logo
Quinta Ace 30-160
quinta -ace-30-160

Wall Hung Boilers

Quinta Ace 30-160

The Quinta Ace is a market-leading series of high-efficiency wall hung condensing boilers with low NOx emissions. The extremely compact design enables individual installation or as part of a multi-boiler cascade or rig system. The Quinta Ace wall hung boilers are suitable for use on both sealed and open-vented (excluding the Quinta Ace 135 & 160) installations and are perfect for both new and retrofit installations. Available in 30, 45, 55, 65, 90, 115, 135 and 160kW models.

Features and Benefits

High-efficiency

High-efficiency wall hung boiler up to 99.6% Gross Calorific Value (GCV) at 50/30 (30% part load) – greater than average energy savings

Compact size

Small dimensions and lightweight design – easy to install in smaller spaces

Low emissions

Low NOx Annual Emissions levels from 22mg/kWh (0% 02, dry) (Class 6) – low pollutant emissions meet environmental regulations

Clean, trouble-free operation

Premix down-firing gas burner and one-piece cast aluminium heat exchanger

Advanced controls

Built-in advanced boiler control and calorifier control fully modulating 18-100% (5:1), 0-10V operation, on/off (volt free enable) – built-in flexibility for easy installation

Improved comfort

Quiet operation less than 52dba
Show more
Show less

Product Literature

Specification Guides

Specification Guides

Product Fiche

Product Fiche

Quinta Ace 30 160

BIM

BIM

Quinta Ace 30 160

Technical Specification

Model

30

45

55

65

90

115

135

160

Performance
Nominal heat output central heating 8.0–29.8 8.0–40.8 11.1–55.3 12.0–61.5 14.1–84.2 18.9–103.9 31.5–128.1 31.5–152.1
operation @ 80/60°C kW (min–max)*
Nominal heat output central heating9.1–30.9 9.1–42.4 12.3–58.6 13.5–65.0 15.8–89.5 21.2–109.7 34.7–136.1 34.7–161.6
operation @ 50/30°C kW (min–max)*
Nominal input (Hi) (min–max) 8.2–30 8.2–41.2 11.3–56.5 12.2–62.014.6–86.0 9.6–107.0 32–131 32–156
Efficiency
SBEM seasonal efficiency GCV 97.62% 97.64% 96.04% 97.58% 95.65% 95.44% 96.12% 95.90%
Efficiency – full load 100% NCV99.4%99.1%97.8% 99.2% 97.9% 97.1% 97.8% 97.5%
Efficiency – part load 30% NCV 110.4% 110.6% 108.7% 110.4% 108.1% 108% 108.8% 108.5%
Eco design useful efficiency @ 80/60°C 89.6% 89.3% 88.1% 89.4% 88.2% 87.5% 88.1% 87.8%
(100% full load) GCV
Eco design useful efficiency @ 50/30°C 99.5% 99.6% 97.9% 99.5% 97.4% 97.3% 98.0% 97.8%
(30% part load) GCV
Energy labelling seasonal space
efficiency GCV 94% 94% 92% 94%N/a N/a N/a N/a
ErP efficiency rating A A A A N/a N/a N/a N/a
Annual energy consumption Gj 91 125 173 188 N/a N/a N/a N/a
Gas
Standard fuel Natural gas Natural gas Natural gas Natural gas Natural gas Natural gas Natural gas Natural gas
Optional fuel adjustment – see installationLPG (propane) LPG (propane) LPG (propane) LPG (propane) LPG (propane) LPG (propane) LPG (propane) LPG (propane)
and service manual
Gas consumption NG m3/h 0.9–3.2 0.9–4.4 1.2–6.0 1.3–6.6 1.5–9.1 2.1–11.3 3.4–13.9 3.4–16.5
Gas consumption LPG m3/h 0.4–1.2 0.4–1.7 0.5–2.3 0.5–2.5 0.9–3.5 0.9–4.4 1.4–5.3 1.4–6.3
Min/max gas inlet pressure NG mbar 17–25 17–25 17–25 17–25 17–25 17–25 17–25 17–25
Min/max gas pressure LPG mbar 37–50 37–50 37–50 37–50 37–50 37–50 37–50 37–50
Gas connection size BSP inches¾" male thread ¾" male thread ¾" male thread ¾" male thread ¾" male thread ¾" male thread 1" male thread 1" male thread
Gas
Flue diameter mm I/D 80 80 100 100 100 100 100 100
Air inlet diameter mm I/D 125 125 150 150 150 150 150 150
Min/max flue gas mass flow rate kg/h 14–50 14–69 19–93 21–104 28–138 36–178 57–233 57–277
Min/max flue gas temperature °C 30–65 30–67 30–68 30–68 30–68 30–72 32–63 32–66
Max counter pressure Pa 70 150 120 100 160 220 200200
Hydraulics
Water content litres 4.3 4.3 6.4 6.4 9.4 9.4 17.0 17.0
Resistance @ 15°C ∆T mbar 124 203 231 290 272444 224302
Hydraulic resistance @ 20°C ∆T mbar 70 114 130 163 153 250 126 170
Nominal flow rate @ 15°C ∆T l/s0.48 0.65 0.88 0.97 1.34 1.66 2.04 2.43
Nominal flow rate @ 20°C ∆T l/s 0.36 0.49 0.66 0.74 1.01 1.24 1.53 1.82
Condensate connection 32mm 32mm 32mm 32mm 32mm 32mm 32mm 32mm
Connection size BSP 1¼" male thread 1¼" male thread 1¼" male thread 1¼" male thread 1¼" male thread 1¼" male thread 1¼" male thread 1¼" male thread
Standard operating temperature** °C 20–90 20–90 20–90 20–90 20–90 20–90 20–90 20–90
Max operating temperature °C 90 90 90 90 90 90 90 90
High limit temperature °C 110 110 110 110 110 110 110 110
Max water operating pressure bar 4 4 4 4 4 4 4 4
Min water operating pressure bar0.8 0.8 0.80.8 0.8 0.8 0.80.8
Min operating pressure bar (OV)** 0.3 o/v0.3 o/v 0.3 o/v 0.3 o/v 0.3 o/v 0.5 o/v N/a N/a
General
Total weight (including packaging) kg60.5 60.5 66.5 66.5 76.5 76.5 147 147
Min mounting weight without
front panel kg 50 50 56 56 65.2 65.2 123 123
Dimension mm (WxHxD) 500x750 x500 500x750 x500 500x750 x500 500x750 x500 500x750 x500 500x750 x500 600x1045 x602 600x1045 x602
NOx Annual Emissions BREEAM EN15502 - 24 24 23 23 23 23 24 22
NG mg/kWh (dry, 0% O2) Class 6***
BREEAM Credits *** 2 2 2 2 2 2 2 2
Noise levels dB(A) at 1 metre 38.3 45.1 46.7 46.7 51.6 51.1 59.5 59.5
Eco design sound power levels
LWA indoors dB 46 53 55 55 60 59 68 68
Standby heat loss kW 0.101 0.101 0.110 0.110 0.123 0.123 0.191 0.191
Electrical
Nominal power supply 230vx1ph x50hz 230vx1ph x50hz 230vx1ph x50hz 230vx1ph x50hz 230vx1ph x50hz 230vx1ph x50hz 230vx1ph x50hz 230vx1ph x50hz
Power consumption w 19–40 20–75 26–81 26–89 26–114 32–182 47–199 47–275
Modulating input v dc 0–100–100–100–100–100–10 0–100–10
Controls voltage 24 (max 4va) 24 (max 4va) 24 (max 4va) 24 (max 4va) 24 (max 4va) 24 (max 4va) 24 (max 4va) 24 (max 4va)
Electrical protection index VAC X4D X4D X4D X4D X4D X4D X1B X1B

*Gas consumption based on lower heating value under standard heating conditions: T=288.15K, p=1013.25mbar. Gag 30.33, G25 29.25, G31 88.00 MJ/m3
**Open vented option maximum operating temperature 75°C

Related Articles

Remeha Commercial Products and Solutions

Case study

Archbishop Ilsley School

Birmingham secondary school improves energy efficiency with heating and hot water upgrade
Molineux Stadium and Training Ground Case Study - Remeha Commercial Projects

Case Study

Molineux Stadium and Training Ground

Remeha boilers score high with Wolves Premier League Club.

Contact your Dedicated Expert

Get in touch with our experts for product enquiries or to get a quote.